Fire CompartmentationSurvey

A fire compartmentation survey inspects the fire-resisting walls, floors and cavity barriers that divide a building into compartments, and the fire stopping that seals every pipe, cable and duct passing through them. Each element is checked against the Building Regulations, the manufacturer installation specification and its fire test evidence.

  • Visual and destructive testing
  • Existing buildings and new works
  • 30 years in passive fire protection

Request a survey quote

Two questions about the building, then where to send the quote.

Step 1 of 2 · the building

Your details are only used to answer this request.

Surveyor photographing an unsealed hole around a cable tray in a compartment wall
Surveyor photographing an unsealed hole around a cable tray in a compartment wall

What does a fire compartmentation survey check?

A compartmentation survey checks the elements that keep fire and smoke inside the compartment where it starts. The surveyor works above ceilings, inside risers and behind access panels, because that is where breaches are hidden.

ElementWhat is checked
Compartment wallsContinuous from floor slab to soffit, with no gaps above the ceiling line and no unsealed openings.
Compartment floorsEvery service penetration through the slab sealed with a tested fire stopping product.
Fire stoppingCorrect product for the service type, installed to the manufacturer detail, to the depth and width the fire test evidence requires.
Cavity barriersPresent where cavities cross compartment lines, continuous, and tight to the surfaces they close off.
Risers and ductsSealed at each floor or enclosed in fire-resisting construction.
Fire doors in compartment wallsFlagged for a full fire door inspection where the door assembly itself needs assessing.

The background to each element is in Fire Compartmentation.

Is a fire stopping survey the same as a compartmentation survey?

Yes. Fire stopping is the seal around a service where it passes through a compartment wall or floor, so it is part of the compartment and is surveyed with it. A fire stopping survey and a compartmentation survey describe the same inspection. What fire stopping is made of, and where it is required, is covered in Fire Stopping.

How is fire stopping tested?

Fire stopping is tested visually and, where the visual check cannot confirm it, destructively.

  1. Visual inspection. Each penetration is located and compared with the manufacturer installation detail for that product and service type. Defects are photographed.
  2. Destructive testing. A small section of sealant or batt is cut out to confirm the product, its depth and what is behind it.
  3. Evidence check. The installed seal is matched to its fire test evidence, or to a solution Approved Document B accepts. A seal with no evidence of performance for that service and substrate cannot be confirmed as compliant, and is recorded as such even if it looks complete.
Section of fire stopping sealant cut out to check its depth during a destructive test
Destructive testing confirms the product, depth and backing of a seal.

Can fire stopping be inspected during construction?

Yes. Veritas inspects ongoing works as well as completed buildings, checking installed fire stopping against the manufacturer installation details and fire test evidence before ceilings and boards close it in.

When do you need a compartmentation survey?

  • The fire risk assessment recommends one, usually because the assessor could not confirm compartmentation from a non-destructive survey.
  • A Type 2 or Type 4 assessment is needed. See Fire Risk Assessment Types 1 to 4.
  • Compartmentation is in doubt in a block that relies on a Stay Put Policy, which only works while compartmentation holds.
  • Services have been added or rerouted, leaving new holes in compartment walls and floors.
  • A building is changing hands and the buyer or lender needs evidence of its passive fire protection.

Cavities that cross compartment lines need cavity barriers; the survey checks they are present and continuous.

What is in the survey report?

Every defect is located, photographed and given a remedial action. Data is collected electronically on site. Budgeted cost plans for the remedial works are available on request.

Example findingExample
Location
Level 2, plant room, north wall
Element
Compartment wall: cable tray penetration
Finding
Opening around cable tray filled with expanding foam with no fire test evidence
Standard
Manufacturer installation detail and fire test evidence
Action
Remove foam, install a tested batt and sealant system, re-inspect
Status
Action required
Illustrative example of how a finding is recorded. Not from a real inspection.

Asset registers and location plans

Veritas also produces registers and location plans for fire stopping, fire doors, structural fire protection and cavity barriers, so each element can be found, maintained and re-inspected.

How much does a compartmentation survey cost?

The price depends on the floor area, the number of risers and ceiling voids to open, how much destructive testing is needed and whether the building is occupied. [typical price range or day rate: to confirm] Send the address and the areas to survey for a quote.

Background reading

What happens after you ask for a quote

Four steps from the first message to the report on your desk.

  1. Tell us about the building

    Choose the inspection, give the building postcode, then where to send the quote.

  2. Receive a quote

    We price the work from what you send and reply with a quote.

  3. Inspection on site

    The inspector works through the building, opening up where the inspection needs it.

  4. The written report

    Defects located, photographed and given remedial actions, with budgeted cost plans on request.

Compartmentation surveys, answered

Is a compartmentation survey a legal requirement?

Not by name. The law requires the Responsible Person to assess fire risk and keep fire precautions maintained under the Regulatory Reform (Fire Safety) Order 2005. A compartmentation survey is how that is evidenced when the fire risk assessment cannot confirm, from a non-destructive look, that compartment walls, floors and fire stopping are intact.

Does the survey damage the building?

Destructive testing removes small sections of fire stopping, or lifts ceiling tiles and access panels, to see what is behind them. Visual inspection alone leaves nothing to make good.

Do you carry out the remedial work?

No. Veritas Inspections inspects and reports. It does not install, so the findings are independent of whoever fitted the fire stopping. Budgeted cost plans for the remedial works are available on request.

Book a compartmentation survey

Send the building address, the floors or areas to survey, and whether the building is occupied.